Well Pressure Tank Size Calculator
Enter the pump's flow and your switch setting. You get the minimum total tank volume, the drawdown behind it, and — if you enter your tank — how long your pump runs per cycle.
Pressure tank size calculator
This tool is for educational guidance and does not replace an onsite diagnosis. Method: Water Well Journal (minimum run time and drawdown) and The Driller (Boyle's law with absolute pressures). Assumes constant pump flow and ignores temperature — round up, and check the tank maker's drawdown chart.
The method
- Drawdown needed = pump flow (GPM) × minimum run time. Water Well Journal uses 1 minute for motors under 2 HP and 2 minutes at 2 HP and above.[1] Franklin Electric also asks for at least 1 minute of running per start.[2]
- Drawdown factor = P1 × (1/P2 − 1/P3), in absolute pressure: P1 = precharge, P2 = cut-in, P3 = cut-out, each plus atmospheric pressure (14.7 psi at sea level). This is Boyle's law as published in The Driller.[3]
- Minimum total volume = drawdown needed ÷ drawdown factor.
The result also shows Water Well Journal's simpler factor, 1 − (cut-in + 14.7) ÷ (cut-out + 14.7), which assumes the precharge equals the cut-in. With the usual precharge 2 psi below cut-in, our number comes out slightly larger.
Elevation: if you enter one, atmospheric pressure is estimated with the U.S. Standard Atmosphere formula. The Driller's example shows altitude increases drawdown slightly (about 1 gallon on an 85-gallon tank at 6,000 ft).[3]
Other well calculators: see all tools.
Check the answer
Water Well Journal's published example — 18 GPM, 2 HP, 45/65 psi — needs 36 gallons of drawdown and a 144-gallon tank using their formula.[1] Enter 18 GPM, "2 HP or more", a custom 45/65 setting and a 45 psi precharge to reproduce it.
Assumptions and limits
- Pump flow is treated as constant through the cycle; real pumps deliver a little less near cut-out.
- Temperature and gauge error are ignored.
- Tank models have a maximum share of their volume that can be water; Amtrol says to check it.[4] Residential settings are normally inside it.
- Constant-pressure systems use different tank rules — see constant-pressure systems.
This tool is for educational guidance and does not replace an onsite diagnosis.
Sources
- Water Well Journal. Tank Selection by the Numbers — David L. Kill, PE (April 19, 2022). Accessed Sept. 28, 2026.
- Franklin Electric. Submersible Motors: Application, Installation & Maintenance (AIM) Manual, 60 Hz. Accessed Sept. 28, 2026.
- The Driller. How to Calculate and Control Pressure Tank Drawdown — Bob Pelikan (Feb. 1, 2006). Accessed Sept. 28, 2026.
- Amtrol. Sizing the Well-X-Trol (commercial sizing handbook). Accessed Sept. 28, 2026.
We cite manufacturer documentation and public agencies first. Read how we choose and check sources.